USER GUIDEEnglish0044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:38 Page 1
The system will signal Fault while in this modeThe LASER is used to align the Detector with the Reflector. Itis an approximate alignment tool only. Af
Commissioning‘Auto’ Alignment and ‘Set’ 0/100 (Calibrate)9. ‘Set’ 0/100 (Calibrate)• Select ‘Auto’ to automaticallyalign the infrared beam• Signal Str
CommissioningAlignment Status10. System is Aligned• It is recommended to set the system back to ‘Lo A’ mode• Green LED on Detector will flash every 10
In UseSettings and Final TestsFire ThresholdHow to change thethreshold at which theDetector will detect a FireDelay 1 (Fire)Fire / Fault DelayHow to c
In UseSettings and Final TestsDetector Fire LED TestDetector will signal Fire,System Controller will stayNormal.Press to exitwithout performing the te
In UseCleaning the SystemCleaning the SystemThe system will automatically compensate for dustbuild-up by changing the Compensation Level.However, it i
Re-Finding a System - After Adding or Removing DetectorsIn Use60 seconds• Press tick to enable found Detectors• Any unused Detector channels are switc
TroubleshootingSystem in Fault/Trouble17• If a Fault/Trouble is indicated at the System Controller:• Refer to manufacturer for further technical assis
TroubleshootingError CodesDetector Not FoundSystem Controller could not findDetector. Also displayed duringpower up.• Wait 45 seconds for system topow
TroubleshootingError CodesCannot Zero During ‘S-00’in ‘Set’The Reflector was notcovered or the Detector wasnot aligned onto the Reflector.• Ensure Ref
IMPORTANTPLEASE NOTE: The infrared beam path MUST be keptclear of obstructions at all times!Failure to comply may result in the Detector initiating aF
If it is not possible to see the LASER because ofthe installation environment (for example, if youcannot see the Reflector from the SystemController o
TroubleshootingHome PositionIf it is not known where the beam is pointing, use Home Positionto automatically steer the infrared beam to approximately
Display and IndicatorsLCD Icon LayoutLatched / ResetDegreesSecondsSignal StrengthUser PromptCompensation LevelMetresFeetFireTransmitSignal StrengthRec
Display and IndicatorsDetector and System Controller Status Indicators12345DetectorIndicator flashes every 10 seconds.NORMAL: GREENFAULT: YELLOWFIRE:
Menu LayoutUser MenuController parameters• Press in this menu to enter the Pass Code• Press to put the system into SleepDetector parameters240044-034-
Menu LayoutUser Menu - DescriptionsController parametersDetector parametersPower Mode‘Hi A’ or ‘Lo A’System ControllerStatusSystem ControllerSoftware
• The Pass Code must be entered to access the Engineering Menu• The menu is navigated by using keys to move the cursor.• Items are selected by using•
Menu LayoutDetector Settings** WARNING: ENGINEERING USE ONLY. ALTERING MAY CAUSE MALFUNCTIONSet TX Power **Set Compensation Level **Set RX Gain **Set
Menu LayoutSystem Controller SettingsChange Pass CodePower ModeUnits of Measurement• Units of MeasurementChanges between ‘Metric’ and ‘Imperial’• Chan
System InformationOperating Parameters and DimensionsDimensionsWidth, in (mm)Height, in (mm)Depth, in (mm) Weight, lb (kg)ParameterDescriptionDefaultP
ContentsInstallation4 General Information5 Wiring Diagrams6 Fitting the ProductCommissioning7 Apply Power and Enter Pass Code8 Finding Detectors and S
Approval InformationTerritory-Specific Approval InformationEuropean Approval InformationComplies with EN54-12 for sensitivity levels between 25%and 35
General InformationInstallation• Check the beam spacing against local regulations• Position beam as high as possible, but with a minimumdistance of 0.
Wiring DiagramsInstallationWiring for all other System Controllers (where more than one SystemController is on one zone)(Not to be used for UL region
Fitting the ProductInstallationLED indicator must face downward60044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:38 Page 6
Apply Power and Enter Pass CodeCommissioning1. Apply power• ‘E-02’ at this stage isnormal2. Enter Pass Code to Access Engineering MenuPress for Pass C
Finding Detectors and Selecting Power ModeCommissioning3. Find Detectors60 seconds• Press tick to enable ‘Found’ Detectors• Any unused Detector channe
Select Detector and DistanceCommissioning• Select 8-50m (default) or 100m• It is possible to set the range of eachindividual Detector6. Select Distanc